12/23/2025
ADDENDUM NO. 1
PROJECT:
DESCRIPTION:
BID PACKAGE RELEASE NUMBER:
Saline Area Schools – 2022 Bond Program –
Addendum No.1
BP #5 (Electrical Re-Bid)
BID PROPOSAL DUE DATE/TIME: 2:00 PM, Tuesday, January 6th, 2026
The following clarifications and/or Changes made to the Contract Documents are hereby
made part of the Contract Documents.
The general character of the Work clarified or revised by this Addendum shall be the
same as required by the complete set of Contract Documents. All incidentals required in
connection with the Work of this Addendum shall be included in the Scope of Work even
though not specifically specified.
All bidders shall be held responsible to review the Addendum and to include in its Bid
Proposal all Work reasonably inferred to be included in its Scope of Work.
Acknowledge receipt of this Addendum in the space provided on the Bid Proposal
Form.
A. Architect/Engineering Documentation
1. VE Markups as issued by Kingscott Associates, Inc. / SES.
B. Division 00 – Bidding and Contract Requirement Modifications:
1. Section 002416 – Scope of Work – Bid Category Specific Notes
i. Bid Category 32 – Landscaping (Not Re-issued)
1. Add Note 27 – Furnish and install topsoil, seed and mulch
in areas outside of the clearing and grubbing area affected
by site logistics. See site logistics plan for more detail.
Assume 3,000 sf of area for the purpose of this bid.
Saline Area Schools – 2022 Bond Program
Bid Release No. 5 Heritage School Additions & Renovations
Addendum No. 001
Page 1 of 2
2. Add Note 28 – This bid category is to include an allowance
of $15,000.
2. Section 004126 – Bid Form
i. Revised and re-issued with additional alternates. (See VE
Markups).
C. Pre-Bid Conference Sign-in Sheet and Presentation
END OF SECTION
Saline Area Schools – 2022 Bond Program
Bid Release No. 5 Heritage School Additions & Renovations
Addendum No. 001
Page 2 of 2
l jh
VE SCOPE: WHERE HALF SHADED FIXTURES
ARE INDICATED, PROVIDE SAME FIXTURE
TYPE WITH EMERGENCY BATTERY OPTION.
COPPER FEEDER SCHEDULE
FEEDER COND.
(AMPS)
SIZE
2 WIRE WITH GROUND
FEEDER COND.
(AMPS)
SIZE
3 WIRE WITH GROUND
FEEDER COND.
(AMPS)
SIZE
4 WIRE WITH GROUND
15S
12
20S
12
2#12, 1#12 GND IN 3/4"C
2#12, 1#12 GND IN 3/4"C
15
12
20
12
3#12, 1#12 GND IN 3/4"C
3#12, 1#12 GND IN 3/4"C
15N
12
20N
12
4#12, 1#12 GND IN 3/4"C
4#12, 1#12 GND IN 3/4"C
25S
10
2#10, 1#10 GND IN 3/4"C
25
10
3#10, 1#10 GND IN 3/4"C
25N
10
4#10, 1#10 GND IN 3/4"C
30S
10
2#10, 1#10 GND IN 3/4"C
30
10
3#10, 1#10 GND IN 3/4"C
30N
10
4#10, 1#10 GND IN 3/4"C
35S
8
2#8, 1#10 GND IN 3/4"C
35
8
3#8, 1#10 GND IN 3/4"C
35N
8
4#8, 1#10 GND IN 3/4"C
40S
8
2#8, 1#10 GND IN 3/4"C
40
8
3#8, 1#10 GND IN 3/4"C
40N
8
4#8, 1#10 GND IN 3/4"C
45S
6
2#6, 1#10 GND IN 3/4"C
45
6
3#6, 1#10 GND IN 3/4"C
45N
6
4#6, 1#10 GND IN 1"C
50S
6
60S
4
70S
4
2#6, 1#10 GND IN 3/4"C
2#4, 1#10 GND IN 1"C
2#4, 1#8 GND IN 1"C
50
6
60
4
70
4
3#6, 1#10 GND IN 3/4"C
3#4, 1#10 GND IN 1"C
3#4, 1#8 GND IN 1"C
50N
6
60N
4
70N
4
4#6, 1#10 GND IN 1"C
4#4, 1#10 GND IN 1 1/4"C
4#4, 1#8 GND IN 1 1/4"C
80S
3
90S
2
100S
1
2#3, 1#8 GND IN 1"C
2#2, 1#8 GND IN 1"C
2#1, 1#8 GND IN 1 1/4"C
80
3
90
2
100
1
3#3, 1#8 GND IN 1"C
3#2, 1#8 GND IN 1 1/4"C
3#1, 1#8 GND IN 1 1/4"C
80N
3
90N
2
100N
1
4#3, 1#8 GND IN 1 1/4"C
4#2, 1#8 GND IN 1 1/2"C
4#1, 1#8 GND IN 1 1/2"C
110
2
125
1
3#2, 1#6 GND IN 1 1/4"C
3#1, 1#6 GND IN 1 1/4"C
110N
2
125N
1
4#2, 1#6 GND IN 1 1/4"C
4#1, 1#6 GND IN 1 1/2"C
150
1/0
3#1/0, 1#6 GND IN 1 1/2"C
150N
1/0
4#1/0, 1#6 GND IN 2"C
175
2/0
3#2/0, 1#6 GND IN 1 1/2"C
175N
2/0
4#2/0, 1#6 GND IN 2"C
200
3/0
3#3/0, 1#6 GND IN 2"C
200N
3/0
4#3/0, 1#6 GND IN 2"C
225
4/0
3#4/0, 1#4 GND IN 2"C
225N
4/0
4#4/0, 1#4 GND IN 2 1/2"C
250
250
3-250 KCMIL, 1#4 GND IN 2"C
250N
250
4-250 KCMIL, 1#4 GND IN 2 1/2"C
300
350
3-350 KCMIL, 1#4 GND IN 2 1/2"C
300N
350
4-350 KCMIL, 1#4 GND IN 3"C
350
500
3-500 KCMIL, 1#3 GND IN 3"C
350N
500
4-500 KCMIL, 1#3 GND IN 3 1/2"C
400
600
3-600 KCMIL, 1#3 GND IN 3 1/2"C
400N
600
4-600 KCMIL, 1#3 GND IN 4"C
450
2-4/0
(2) 3#4/0, 1#2 GND IN 2"C
450N
2-4/0
(2) 4#4/0, 1#2 GND IN 2 1/2"C
500
2-250
(2) 3-250 KCMIL, 1#2 GND IN 2 1/2"C
500N
2-250
(2) 4-250 KCMIL, 1#2 GND IN 2 1/2"C
600
2-350
(2) 3-350 KCMIL, 1#1 GND IN 2 1/2"C
600N
2-350
(2) 4-350 KCMIL, 1#1 GND IN 3"C
NOTES:
1. AMPACITIES FOR FEEDER SIZES ARE BASED ON N.E.C. CODE 110-14. (TERMINATION PROVISIONS FOR EQUIPMENT RATED 100A OR LESS ARE RATED FOR USE WITH CONDUCTORS RATED 60°C. TERMINATION PROVISIONS FOR EQUIPMENT RATED GREATER THAN
100A ARE RATED FOR USE WITH CONDUCTORS RATED 75°C.).
2. CONDUIT FILL IS BASED ON 40% FILL USING SINGLE CONDUCTOR BUILDING WIRE OF INSULATION TYPES THHN, THWN, THWN-2, XHH, XHHW, AND XHHW-2 IN RMC. FOR OTHER RACEWAY TYPES REFER TO APPROPRIATE N.E.C. APPENDIX C TABLES.
3. EQUIPMENT GROUND SIZING BASED ON N.E.C. TABLE 250.122.
DRY TYPE TRANSFORMER SCHEDULE - 480VD TO 208Y/120V
KVA
3
PRIMARY
BREAKER
OR FUSE
FEEDER
(AMPS)
10A
10TP
4.5
15A
15TP
PRIMARY WIRE SIZE
3#12 & 1#12 GND IN 3/4"C
3#12 & 1#12 GND IN 3/4"C
SECONDARY
BREAKER
OR FUSE
FEEDER
(AMPS)
15A
15TS
20A
20TS
SECONDARY WIRE SIZE
4#12 & 1#12 GND IN 3/4"C
4#12 & 1#12 GND IN 3/4"C
6
12A
12TP
3#12 & 1#12 GND IN 3/4"C
25A
25TS
4#10 & 1#10 GND IN 3/4"C
9
20A
20TP
3#12 & 1#12 GND IN 3/4"C
35A
35TS
4#8 & 1#10 GND IN 3/4"C
15
25A
25TP
3#10 & 1#10 GND IN 3/4"C
60A
60TS
4#6 & 1#10 GND IN 1"C
22
35A
35TP
3#8 & 1#10 GND IN 3/4"C
80A
80TS
4#4 & 1#8 GND IN 1 1/4"C
30
45A
45TP
3#8 & 1#10 GND IN 3/4"C
110A
110TS
4#2 & 1#6 GND IN 1 1/4"C
45
70A
70TP
3#4 & 1#8 GND IN 1"C
175A
175TS
4#2/0 & 1#6 GND IN 2"C
75
125A
125TP
3#1 & 1#6 GND IN 1 1/4"C
300A
300TS
4-350 KCMIL & 1#4 GND IN 3"C
NOTES:
1. THE PRIMARY AND SECONDARY BREAKERS OR FUSES ARE LOCATED IN SWITCHBOARD OR PANELBOARD UNLESS SHOWN OTHERWISE.
2. THE SECONDARY NEUTRAL OF DRY-TYPE TRANSFORMERS SHALL BE GROUNDED PER NATIONAL ELECTRICAL CODE AND LOCAL CODE.
3. THIS TRANSFORMER SCHEDULE IS A MASTER LIST. EVERY TRANSFORMER SIZE LISTED MAY NOT BE USED IN EVERY PACKAGE. SEE PLANS FOR ACTUAL SIZES USED.
LIGHTING CONTROLS LEGEND
SYMBOL
DESCRIPTION
SL
LIGHT CONTROL LOCATION
S
SWITCH - SINGLE POLE
S3
SWITCH - THREE WAY
S4
SWITCH - FOUR WAY
TECHNOLOGY SYMBOL LIST
SYMBOL
DESCRIPTION
BELL OUTLET
CAMERA
CR
CARD READER
I
INTERCOM
LOW VOLTAGE PANEL
PUSH BUTTON
SS
SPEAKER - WALL MOUNTED, CEILING MOUNTED
TECHNOLOGY OUTLET - 6" ABOVE COUNTER
TECHNOLOGY OUTLET - FLOOR
TECHNOLOGY OUTLET - WALL
TV
TELEVISION OUTLET
WALL CLOCK - SINGLE FACE
WALL CLOCK - DOUBLE FACE
S
WALL CLOCK AND SPEAKER UNIT
WAP
WIRELESS ACCESS POINT
NOTES:
1. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR BOX AND CONDUIT FOR
ALL DEVICES INDICATED.
2. LOW VOLTAGE CONTRACTOR SHALL PROVIDE EXACT SPECIFICATIONS AND
LOCATIONS OF ALL DEVICES.
TAG
NUMBER
SPACE TYPE
LIGHTING CONTROLS MATRIX
PARAMETERS
SEQUENCE OF OPERATIONS
ELECTRICAL ABBREVIATIONS
ABBREV.
DESCRIPTION
AFF
AWG
A
AF
AT
ATS
AIC
CB
C
CU
CT
DIA
DISC
EWC
EC
EMT
EPO
(E)
FA
FACP
FLA
F
G/GND
GFCI/GFI
HOA
HP
IG
INV
KV
KVA
KW
KWH
LP
MCB
MDP
MLO
MAX
MIN
NEC
NEMA
N/NEU
NF
NC
NO
NIC
PH/Ø
P
PVC
PF
(R)
RP
(RR)
RMC
TBB
XFMR
TYP
UC
UL
UPS
USB
UON
V
VA
W
WP
WG
ABOVE FINISHED FLOOR
AMERICAN WIRE GAUGE
AMPERE
AMPERE FUSE/AMPERE FRAME
AMPERE TRIP
AUTOMATIC TRANSFER SWITCH
AVAILABLE INTERRUPTING CURRENT (AMPS)
CIRCUIT BREAKER
CONDUIT OR CEILING MOUNTED
COPPER
CURRENT TRANSFORMER
DIAMETER
DISCONNECT
ELECTRIC WATER COOLER
ELECTRICAL CONTRACTOR
ELECTRICAL METALLIC TUBING
EMERGENCY POWER OFF
EXISTING ELECTRICAL EQUIPMENT/WORK TO REMAIN
FIRE ALARM
FIRE ALARM CONTROL PANEL
FULL LOAD AMPS
FUSE
GROUND
GROUND FAULT CIRCUIT INTERRUPTER
HAND-OFF-AUTO
HORSEPOWER
ISOLATED GROUND
INVERTER
KILOVOLT
KILOVOLT AMPERE
KILOWATT
KILOWATT HOUR
LIGHTING PANEL
MAIN CIRCUIT BREAKER
MAIN DISTRIBUTION PANEL
MAIN LUG ONLY
MAXIMUM
MINIMUM
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURERS ASSOC.
NEUTRAL
NON-FUSIBLE
NORMALLY CLOSED
NORMALLY OPEN
NOT IN CONTRACT
PHASE
POLE
POLYVINYL CHLORIDE (PLASTIC)
POWER FACTOR
RELOCATED EXISTING ELECTRICAL EQUIPMENT
RECEPTACLE PANEL
REMOVE AND REINSTALL
RIGID METALLIC CONDUIT
TELEPHONE BACKBOARD
TRANSFORMER
TYPICAL
UNDERCOUNTER
UNDERWRITERS LABORATORIES
UNINTERRUPTIBLE POWER SUPPLY
UNIVERSAL SERIAL BUS
UNLESS OTHERWISE NOTED
VOLT
VOLT AMPERE
WATT
WEATHERPROOF
WIRE GUARD
1
CLASSROOM, MULTI-PURPOSE ROOM X X
X
2
CORRIDOR
X
X
X
3
RESTROOM
X
X
4
STORAGE ROOM
5
MECH/ELECTRICAL
6
EXTERIOR EGRESS/SECURITY
LIGHTING
X
X
X
X
X
X
MANUAL ON/AUTOMATIC OFF WITHIN 20 MIN OF OCCUPANTS LEAVING SPACE (VACANCY MODE).
CONTINUOUS DIMMING.
LOCAL CONTROL SWITCH WITH ON/OFF FUNCTION. AUTOMATIC ON TO FULL VIA OCCUPANCY
SENSOR. AUTOMATIC FULL OFF VIA OCCUPANCY SENSOR (VACANCY MODE) WITHIN 20 MIN OF
OCCUPANTS LEAVING SPACE.
LOCAL CONTROL SWITCH WITH ON/OFF FUNCTION. AUTOMATIC ON TO FULL VIA OCCUPANCY
SENSOR. AUTOMATIC FULL OFF VIA OCCUPANCY SENSOR (VACANCY MODE) WITHIN 20 MIN OF
OCCUPANTS LEAVING SPACE.
LOCAL CONTROL SWITCH WITH ON/OFF FUNCTION. AUTOMATIC ON TO FULL VIA OCCUPANCY
SENSOR. AUTOMATIC FULL OFF VIA OCCUPANCY SENSOR (VACANCY MODE) WITHIN 20 MIN OF
OCCUPANTS LEAVING SPACE.
LOCAL CONTROL SWITCH WITH ON/OFF FUNCTION.
MANUAL OVERRIDE SWITCH WITH ON/OFF AND DIM FUNCTION. AUTOMATIC ON TO FULL VIA
SCHEDULED TIME FUNCTION OR PHOTOCELL. AUTOMATIC LIGHT LEVEL REDUCTION TO 70% AFTER
X HOURS VIA SCHEDULED TIME FUNCTION. FULL SHUTOFF VIA SCHEDULED TIME FUNCTION OR
PHOTOSENSOR.
NOTES:
1. ALL OCCUPANCY SENSORS SHALL HAVE AN ADDITIONAL DRY CONTACT FOR TIE-IN TO HVAC EQUIPMENT CONTROLS.
DISTRIBUTED LIGHTING CONTROLS SYSTEM (DRIVERS, SWITCHES, OCCUPANCY SENSORS, ETC.) WILL NETWORK
BACK TO A SINGLE SYSTEM CONTROLLER. A NETWORK CONNECTION (VIA BACNET/IP, BACNET MS/TP, OR THROUGH
SCHOOL'S NETWORK) BETWEEN THE BMS FRONT-END AND THE LIGHTING CONTROLLER SHALL BE PROVIDED BY THE
TCC (IF DIRECT TO CONTROLLER).
2. PROVIDE PLUG LOAD POWER PACKS FOR CONTROLLED RECEPTACLES AND INTEGRATE FUNCTIONALITY WITH
OCCUPANCY SENSORS.
3. ALL EXTERIOR LIGHTING (NON-SITE POLES) SHALL BE CONTROLLED BY BMS SYSTEM.
TYPE
L1
L2
L3
L4
L5
L6
L7
L8
L9
L10
L11
S1
X1
DESCRIPTION
2' X 4' RECESSED FLAT PANEL.
SAME AS "L1" WITH DIFFERENT LUMEN PACKAGE.
4" DIRECT-ONLY LINEAR PENDANT - 4' STRIP.
2' X 4' RECESSED TROFFER - HIGH ABUSE.
SURFACE-MOUNT DECORATIVE FIXTURE - 24" DIA. HEX.
4" RECESSED LINEAR - 4' SECTION.
SAME AS "L6" WITH DIFFERENT LUMEN PACKAGE.
4" ROUND RECESSED DOWNLIGHT.
4" SURFACE MOUNT DIRECT-ONLY LINEAR - 2' SECTION.
4" SURFACE MOUNT DIRECT-ONLY LINEAR.
4" ROUND RECESSED DOWNLIGHT - WET LISTED.
EXTERIOR WALL PACK.
EXIT SIGN.
MANUFACTURER
LITHONIA LIGHTING
LITHONIA LIGHTING
LITHONIA LIGHTING
KENALL
EUREKA LIGHTING
FINELITE
FINELITE
GOTHAM LIGHTING
LITHONIA LIGHTING
FINELITE
GOTHAM LIGHTING
LITHONIA LIGHTING
LITHONIA LIGHTING
MODEL
SPX 2x4 4800LM 80CRI 35K LUGR MVOLT
SPX 2x4 4000LM 80CRI 35K LUGR MVOLT
CLX L48 4000LM SEF RDL MVOLT 35K 80CRI
HSEDI 24 45TD 27/65K8 ATW DV 2F 4H SYM
4820D 24 LED REG
HP4 R D XX V 835 F 277 SC OTI-1% FE
HP4 R D XX B 835 F 277 SC OTI-1% FE
EVO4 35/02 AR MD LSS
CLX L24 2000LM SEF RDL MVOLT GZ10 35K 80CRI
HP4 SM D XX H 835 F 277 SC OTI-1% FE
EVOSH4 35/10 DFF SMO MVOLT EZ1
WDGE1 LED P2 40K 80CRI VF MVOLT SRM DDBXD
LQM S W 3 R 120/277 EL N M6
LUMINAIRE SCHEDULE
WATTAGE
34 W
27 W
26 W
45 W
37 W
9W
5W
8W
15 W
7W
9W
15 W
1W
LUMENS
4800
4000
4000
4000
3000
932/FT
479/FT
250
1500
725/FT
1000
TBD
RED
VOLTAGE
MVOLT
MVOLT
MVOLT
MVOLT
277
277
277
MVOLT
MVOLT
277
MVOLT
MVOLT
277
CCT
35K
35K
35K
27-65K
35K
35K
35K
35K
35K
35K
35K
40K
35K
CRI
80+
80+
80+
80+
80+
80+
80+
80+
80+
80+
80+
80+
80+
REMARKS
COORDINATE CUSTOM FIXTURE SPECIFICATONS WITH MANUFACTURER.
PROVIDE WITH (2) ADDITIONAL DRIVERS FOR FUTURE MAINTENANCE.
WATTAGE SHOWN IS PER LINEAR FOOT. REFER TO LIGHTING PLANS FOR RUN LENGTHS.
WATTAGE SHOWN IS PER LINEAR FOOT. REFER TO LIGHTING PLANS FOR RUN LENGTHS.
WATTAGE SHOWN IS PER LINEAR FOOT. REFER TO LIGHTING PLANS FOR RUN LENGTHS.
REFER TO PLANS FOR MOUNTING STYLE, DIRECTIONAL ARROWS, AND NUMBER OF FACES.
ALTERNATE MANUFACTURER | MODEL #1
COLUMBIA - NBT-24-80-35-L048-ED1-U
COLUMBIA - NBT-24-80-35-L040-ED1-U
COLUMBIA - MPS4-35LW-CN-ED1-U
VISCOR - VRU2X4/LED835K055LUNV
LIGHTING ELEMENTS - ATMOS-H-DS-D-MD-35K
LITECONTROL - 4L-XX-D-4-REG-D900-D01-1C-UNV
LITECONTROL - 4L-XX-D-4-REG-D900-D01-1C-UNV
PRESCOLITE - LTR-4RD-H-06L-DM1-35K8MD
COLUMBIA - MPS2-35MW-CN-ED1-U
LITECONTROL - 4L-S-D-XX-35K9-D720-D01-1C-UNV
PRESCOLITE - LTR-4RD-H-SL-DM1-35K8MD
BEACON - VPW-48L-15-4K8-4F-UNV
COMPASS - CAR
POWER SYMBOL LIST
SYMBOL
DESCRIPTION
CONDUIT DOWN
CONDUIT UP
C
CORD REEL
DISCONNECT SWITCH - NON-FUSED
DISCONNECT SWITCH - FUSED
DISCONNECT SWITCH - COMBINATION MOTOR STARTER
FB
FLOOR BOX
ELECTRICAL PANEL
GROUNDING ROD
GROUND
GROUNDING BAR
J
JUNCTION BOX
M
METER
MOTOR - SINGLE PHASE
MOTOR - THREE PHASE
SM
MOTOR RATED SWITCH
PT
POKE-THRU
RECEPTACLE - DUPLEX TYPE
CL
USB
RECEPTACLE - DUPLEX TYPE 6" ABOVE COUNTER
RECEPTACLE - DUPLEX/CONTROLLED LOAD TYPE
RECEPTACLE - DUPLEX/USB COMBINATION TYPE
RECEPTACLE - QUADRUPLEX TYPE
RECEPTACLE - SIMPLEX TYPE
RECEPTACLE - SPECIALTY TYPE
T
TRANSFORMER
VFD
VARIABLE FREQUENCY DRIVE
NOTES:
1. ALL DEVICE RATINGS/SIZES SHALL BE COORDINATED WITH PLANS AND
SCHEDULES.
FIRE ALARM SYMBOL LIST
SYMBOL
DESCRIPTION
F
AUDIBLE DEVICE - CEILING MOUNTED
F
AUDIBLE DEVICE - WALL MOUNTED
C
CARBON DIOXIDE ALARM
CO
CARBON MONOXIDE ALARM
F
COMBINATION AUDIBLE/VISUAL DEVICE - CEILING MOUNTED
F
COMBINATION AUDIBLE/VISUAL DEVICE - WALL MOUNTED
CS
COMBINATION CARBON MONOXIDE ALARM/SMOKE DETECTOR
EXISTING
NEW
COMBINATION FIRE/SMOKE DAMPER
(VERTICAL)
EXISTING
NEW
COMBINATION FIRE/SMOKE DAMPER
(HORIZONTAL)
S
DUCT MOUNTED SMOKE DETECTOR
FAA
FIRE ALARM ANNUNCIATOR PANEL
FACP
FD
FIRE ALARM CONTROL PANEL
FIRE DEPARTMENT COMMUNICATION OUTLET
FS
FLOW SWITCH
H
HEAT DETECTOR
I/O
INPUT/OUTPUT CONTROL MODULE
DH
MAGNETIC DOOR HOLDER
F
MANUAL PULL STATION
SS
SMOKE DETECTOR - WALL MOUNTED, CEILING MOUNTED
S
SMOKE DETECTOR WITH AUDIO
TS
TAMPER SWITCH
F
VISUAL DEVICE - CEILING MOUNTED
F
VISUAL DEVICE - WALL MOUNTED
NOTES:
1. DRAWINGS INDICATE DESIGN INTENT ONLY, FINAL LOCATIONS AND DEVICE
SPECIFICATIONS SHALL BE PROVIDED BY FIRE ALARM MANUFACTURER. REFER
TO PROJECT SPECIFICATIONS FOR APPROVED MANUFACTURERS.
2. FIRE DETECTION AND SIGNALING DEVICES ARE SHOWN FOR COORDINATION
PURPOSES. FINAL SYSTEM DESIGN TO BE PERFORMED BY CONTRACTOR AND
SUPPLIER FOR OFFICIAL SUBMISSION. COORDINATE ALL DEVICE QUANTITIES
AND LOCATIONS WITH SUPPLIER PRIOR TO INSTALLATION. ELECTRICAL
CONTRACTOR SHALL PROVIDE ALL NECESSARY PATHWAYS, POWER SUPPLIES
AND DEVICES PER SUPPLIER CONTRACT DOCUMENTS.
DRAWING INDEX
SHEET
NO
DESCRIPTION
E0.0
ED1.1
ED1.2
ED1.3
ED3.1
ED3.2
ED3.3
EDS1.0
ES1.0
EP1.1
EP1.1A
EP1.2
EP1.3
EP1.3A
EP3.1
EP3.1A
EP3.2
EP3.3
EP3.3A
EL1.1
EL1.1A
EL1.2
EL1.3
EL1.3A
E4.0
E5.0
E6.0
ELECTRICAL GENERAL INFORMATION
ELECTRICAL DEMOLITION PLAN - UNIT 100
ELECTRICAL DEMOLITION PLAN - UNIT 200
ELECTRICAL DEMOLITION PLAN - UNIT 300
ELECTRICAL DEMOLITION ROOF PLAN - UNIT 100
ELECTRICAL DEMOLITION ROOF PLAN - UNIT 200
ELECTRICAL DEMOLITION ROOF PLAN - UNIT 300
ELECTRICAL DEMOLITION SITE PLAN
ELECTRICAL SITE PLAN
ELECTRICAL POWER PLAN - UNIT 100
ELECTRICAL POWER PLAN - UNIT A100
ELECTRICAL POWER PLAN - UNIT 200
ELECTRICAL POWER PLAN - UNIT 300
ELECTRICAL POWER PLAN - UNIT A300
ELECTRICAL ROOF PLAN - UNIT 100
ELECTRICAL ROOF PLAN - UNIT A100
ELECTRICAL ROOF PLAN - UNIT 200
ELECTRICAL ROOF PLAN - UNIT 300
ELECTRICAL ROOF PLAN - UNIT A300
ELECTRICAL LIGHTING PLAN - UNIT 100
ELECTRICAL LIGHTING PLAN - UNIT A100
ELECTRICAL LIGHTING PLAN - UNIT 200
ELECTRICAL LIGHTING PLAN - UNIT 300
ELECTRICAL LIGHTING PLAN - UNIT A300
ENLARGED ELECTRICAL PLANS
ELECTRICAL DETAILS
ELECTRICAL SCHEDULES
DRAWING NOTATION
SYMBOL
DESCRIPTION
1
CONSTRUCTION KEYNOTE NUMBER 1
1
DEMOLITION KEYNOTE NUMBER 1
20
COPPER FEEDER SIZE TAG
(REFER TO FEEDER SCHEDULE)
20
ALUMINUM FEEDER SIZE TAG
(REFER TO FEEDER SCHEDULE)
EQUIPMENT
EQUIPMENT TAG
EXISTING DEVICES OR EQUIPMENT
NEW OR MODIFIED DEVICES OR EQUIPMENT
NEW OR MODIFIED UNDERGROUND WIRING
EXISTING SYSTEM COMPONENT TO BE REMOVED
POINT OF NEW CONNECTION.
LIGHTING FIXTURE TAG
LIGHTING FIXTURE TYPE
L1
INV1
13'-0"
NORMAL CIRCUIT, EMERGENCY
LIGHTING INVERTER, OR
GENERATOR CIRCUIT (MAY NOT
APPEAR ON EVERY TAG)
FIXTURE MOUNTING HEIGHT (MAY
NOT APPEAR ON EVERY TAG)
LIGHTING CONTROL TAG
LIGHTING CONTROL
SPACE TYPE '1'
SCENE SCHEDULE ID 'A' (MAY
1A
NOT APPEAR ON EVERY TAG)
Z1
DAYLIGHTING CONTROL ZONE '1'
(MAY NOT APPEAR ON EVERY
TAG)
NOTE: THE TAG DOES NOT REFLECT THE QUANTITY OF CONTROL DEVICES
REQUIRED IN AREA.
4
E100
4
E300
SECTION NUMBER 4
SHEET E300 ON WHICH
SECTION VIEW IS PLACED
SECTION NUMBER 4
SECTION
SCALE: 1/4" = 1' - 0"
SHEET E100 ON WHICH SECTION IS CUT
(ENLARGED PARTIAL PLAN SIMILAR)
APPLICABLE CODES
AND REGULATIONS
YEAR
CODE
2023
2023
2023
2023
2023
2023
2013
2013
2013
2013
2009
2019
MICHIGAN BUILDING CODE
MICHIGAN ENERGY CODE
MICHIGAN RESIDENTIAL CODE
MICHIGAN REHABILITATION CODE
MICHIGAN ELECTRICAL CODE RULES, PART 8
NATIONAL ELECTRICAL CODE (NFPA 70)
NFPA 20
NFPA 72
NFPA 101
NFPA 110
ICC A117.1 ACCESSIBLE AND USABLE BUILDINGS & FACILITIES
DETROIT ELEVATOR CODE
KALAMAZOO | CHELSEA | GRAND RAPIDS | ROYAL OAK
ISSUANCES
CONSTRUCTION DOCUMENTS
ADDENDUM No. 01
VE MARKUPS
DATE
11.06.2025
11.20.2025
12.22.2025
ALTERNATE MANUFACTURER | MODEL #2
DAY-BRITE - 2SBP3050L-4-UNV-DIM
DAY-BRITE - 2SBP3050L-4-UNV-DIM
DAY-BRITE - FSX440L835-UNV
PACO - PRGA-C8-C8-24-MTG-60-8-35-MV
BASO - HEX-DIR-PDT-COLOR-OP-35K-C80-UNV-010V-0300L-DM-2FT
LEDALITE - 3901L93540QSXX04DE1NNNW
LEDALITE - 3901L93522QSXX04DE1NNNW
LIGHTOLIER - 4RN / C4LETO03935NZ10U / C4RDLCC
ILP - VS2-2L-U-CCTS-FRL
ILP - VS2-2L-U-CCTS-FRL
LIGHTOLIER - 4RN / P4RSL10935WWHZ10U
GARDCO - GWS-A02-840-T4M-UNV-BZ
BARRON EXITRONIX - ILX-RG-AC-WH
TE OF M I CHI
SCOTT E.
TOWNSEND
ENGINEER
No.
6201050400
PROF ESSI ON A L E
11/06/2025
Strategic Energy Solutions®
4000 W. Eleven Mile Road Berkley, MI 48072
Phone 248.399.1900 Fax 248.399.1901
www.sesnet.com
© 2025 SES, INC.
SES Project # 23 0588 02
JOB NO. 2900.09.D
SHEET TITLE
ELECTRICAL GENERAL
INFORMATION
SHEET NO.
E0.0
C KINGSCOTT ASSOCIATES INC.
KALAMAZOO, MICHIGAN
l jh
UNIT 300
UNIT 200
STORAGE
--
T
T
--
--
Room
--
UNIT 300
UNIT 200
S
F
VUV-2
LIFE SKILLS
251
TEACHER STATION IN
SPEECH
250
R1
SURFACE RACEWAY
C
(R)
C
ALL EQUIPMENT IN SPACE ARE FURNISHED BY
OWNER; COORDINATE POWER REQUIREMENTS
WITH CUTSHEETS PRIOR TO ROUGH-IN WORK
MOTOR SKILLS
254
F
TAMPER-RESISTANT
WIREMOLD ALONG WALL
(18" AFF); 5 OUTLETS MIN.
WASHER
& DRYER
F
T
253
F 120VAC FOR IN-
ISLAND GROMMET
REFRIGERATOR
U.C. OVEN &
MICROWAVE
DISHWASHER
J
REFLECT
252
J
F
(E)
GFI GFI
(E)
GFI
ALL NEW POWER SHALL MAKE USE OF
CIRCUITS IN AREA MADE AVAILABLE BY
DEMOLITION WORK.
NOTE: ALL DEVICES SHALL BE GFI-TYPE
(IF NOT PROTECTED AT BREAKER).
FUTURE POWER TO BE
ROUGHED-IN BEHIND PADS
F
J
POWER GENERAL NOTES
1. ALL RECEPTACLES ON EXTERIOR, IN KITCHEN, IN CONCESSION, IN LABORATORY, AND
WITHIN 6'-0" OF SINK OR OTHER WATER SUPPLY SHALL BE READILY ACCESSIBLE GFCI TYPE
RECEPTACLE.
2. REFER TO ARCHITECTURAL FLOOR PLANS AND ELEVATIONS TO VERIFY LOCATION OF
DEVICES.
3. ALL CONDUITS SERVING 120 VOLTS OR GREATER SHALL INCLUDE A GROUND WIRE.
4. ALL CONDUITS SHALL BE ROUTED CONCEALED UNLESS NOTED OTHERWISE.
5. ALL 120 VOLT CIRCUITS SHALL UTILIZE A SEPARATE NEUTRAL.
6. ALL NEW 15- AND 20-AMPERE, 125- AND 250-VOLT NONLOCKING-TYPE RECEPTACLES TO BE
LISTED TAMPER-RESISTANT TYPE THROUGHOUT THIS SCHOOL. EXCEPTIONS TO THIS
INCLUDE RECEPTACLES LOCATED MORE THAN 5.5 FEET ABOVE THE FLOOR AND SINGLE OR
DUPLEX RECEPTACLES FOR DEDICATED APPLIANCES THAT ARE NOT READILY ACCESSIBLE.
ANY EXISTING RECEPTACLES THAT ARE INCLUDED IN THE SCOPE OF RENOVATION WORK
SHALL BE UPDATED PER NEW RECEPTACLE NOTES ABOVE AS WELL.
S
POWER KEYNOTES
R1 REUSE EXISTING BRANCH CIRCUIT WIRING FROM REMOVED UNIT VENTILATOR TO
CONNECT TO NEW UNIT VENTILATOR. NOTE: NO MORE THAN ONE (1) NEW UNIT
VENTILATOR CAN BE ON A 15/20A CIRCUIT BREAKER IN EXISTING PANEL. ALL NEW UNIT
VENTILATORS SHALL BE ON DEDICATED CIRCUITS.
R2 CLASSROOM TEACHER LOCATION. PROVIDE 2-GANG BOX WITH 3/4" CONDUIT FOR POWER
TO CEILING SPACE. COORDINATE WITH TECHNOLOGY DRAWINGS.
R3 PROVIDE NEW 20' CONCRETE-ENCASED ELECTRODE (PER NEC 250.52.3) WITH 1-1/4"
CONDUIT AND 1#4 GROUND TO MAIN BUILDING GROUND SYSTEM. CONNECT TO NEW
BUILDING STEEL AND BACK TO MAIN DISTRIBUTION PANEL.
R4 LOCATION FOR CLASSROOM PROJECTOR. PROVIDE CEILING-MOUNTED DUPLEX
RECEPTACLE. COORDINATE WORK WITH TECHNOLOGY TRADES.
R5 COORDINATE ROUTING OF LOW-VOLTAGE CONDUITS WITH PIPING AND LIGHTING IN AREA;
ALL ROUTING SHALL BE TIGHT TO DECK.
R6 PROVIDE CEILING MOUNTED CORD REEL (MODEL NUMBER "BRYC25163C" BY HUBBEL OR
EQUAL.) CIRCUIT TO GFI BREAKER IN PANEL. REFER TO TECHNOLOGY DRAWINGS FOR
COORDINATION WITH CAMERA IN CEILING AREA.
R7 PROVIDE 3/4" CONDUIT STUBBED TO CEILING SPACE FOR ACCESS CONTROL AT HEADER OF
DOOR. COORDINATE MOUNTING AND CONNECTION REQUIREMENTS WITH TECHNOLOGY
DRAWINGS.
R8 PROVIDE (1) 208V/1P 60A DISCONNECT SWITCH AND POWER CONNECTION FOR KILN;
PROVIDE (1) DEDICATED DUPLEX RECEPTACLE FOR KILN VENT AND CONTROLLER.
COORDINATE AND VERIFY ELECTRICAL REQUIREMENTS OF KILN AND ASSOCIATED
EQUIPMENT WITH MANUFACTURER AND TRADES PRIOR TO INSTALLATION.
KALAMAZOO | CHELSEA | GRAND RAPIDS | ROYAL OAK
M/E B
--
2
E4.0
GYM
--
OFFICE
--
M/E A
--
ATS-EL
EL1
RPKA
VE SCOPE: REMOVE LIFE
SAFETY ATS & PANEL
STORAGE
--
REWIRE EXISTING POWER CONNECTIONS OF
WALK-IN COOLERS, FREEZERS, AND DEFROST
TIMERS TO BE ON NEW STAND-BY PANEL "SR1"
PE STORAGE
--
ENRICHMENT
213
(E)FACP
S (E)
CIRCUIT TO DEDICATED 20A BREAKER
ON (E)RPAA MADE AVAILABLE FROM IT
RACK CIRCUIT RELOCATION
NEW FIRE ALARM CONTROL PANEL WITH
VOICE SYSTEM; CROSS-TIE INTO (E)FACP
OFFICE
--
REWORK EXISTING SURFACE
RACEWAY SO ITS VERTICAL RUN
CAN ACCOMMODATE NEW DOOR
(R)
FB
CONFERENCE
205
1-1/4" PATHWAY TO
WALL (FOR HDMI)
PROVIDE FLOORBOX IN
CONNECTRAC FLOORING;
LOCATE NEAR TABLE LEG
TECHNOLOGY CR
202
MEDIA CENTER
--
(E)RPAA
(E)RPIGA
SR1-12
(E)
(E)
SR1-14
(E)
REWIRE EXISTING POWER CONNECTION
FOR TECHNOLOGY RACK TO BE ON NEW
STAND-BY PANEL "SR1"
WORKROOM
--
COORDINATE EXACT INSTALLATION REQUIREMENTS (BACKBOX TYPE, CONDUIT,
CABLING, LOCATION, ETC.) FOR ALL TECHNOLOGY DEVICES PRIOR TO ROUGH-IN
WORK; REFER TO TECHNOLOGY DRAWINGS AND DETAILS BY OTHERS.
PAINT FLOOR HATCH AROUND ELECTRICAL EQUIPMENT TO INDICATE SERVICE
CLEARANCE. MATCH AND COORDINATE WITH ARCHITECTURAL COLOR PLANS.
KITCHEN
--
SERVERY
--
STUDENT DINING
--
MEN
--
WOMEN
--
JC
--
OFFICE
206
OFFICE
207
TEACHER
PLANNING
205
WKRM
204
ISSUANCES
CONSTRUCTION DOCUMENTS
ADDENDUM No. 01
VE MARKUPS
DATE
11.06.2025
11.20.2025
12.22.2025
ELECTRICAL POWER PLAN - UNIT 200
SCALE: 1/8" = 1'-0"
STAFF DINING
212
UNIT 200
UNIT 100
STAFF T
--
OFFICE
211
OFFICE
209
4th GRADE MUSIC
208
OFFICE
210
VUV-2
S
R1
UNIT 200
UNIT 100
CL
S
C
F
TE OF M I CHI
SCOTT E.
TOWNSEND
ENGINEER
No.
6201050400
PROF ESSI ON A L E
11/06/2025
Strategic Energy Solutions®
4000 W. Eleven Mile Road Berkley, MI 48072
Phone 248.399.1900 Fax 248.399.1901
www.sesnet.com
© 2025 SES, INC.
SES Project # 23 0588 02
KEY PLAN
JOB NO. 2900.09.D
N
SHEET TITLE
ELECTRICAL POWER PLAN - UNIT
200
SHEET NO.
EP1.2
C KINGSCOTT ASSOCIATES INC.
KALAMAZOO, MICHIGAN
l jh
Room
2
BAND
1
UNIT 200
UNIT 100
UNIT 200
UNIT 100
K
L
L3
L3
CR
113
CR
112
CR
114
L3
REMOVE AND REINSTALL
EXISTING FIXTURES IN
NEW 2X2 CEILING GRID
(E)
(E)
(E)
(E)
(E)
UNIT
ELUN1I-T1100
A100
6
L1 S1
LPA1-9
8' - 0"
L3
(E)
(R)
L1
L1
L1
(E)
(R)
RESOURCE ROOM
102
L2
L1
L1 L1
L1
1
EL1-1
CR
101
L3
(E)
(R)
L1
L1
L1
L
L8
EL1-1
(E)
(R)
2
L1
K
L2
L2
L2
X1
L3
(E)
(E)
(R)
L3
TYP
CR
(E)
(E)
103
L
CONNECT TO CORRIDOR
K
LIGHTING IN ADDITION
UNIT A100
UNIT 100
KALAMAZOO | CHELSEA | GRAND RAPIDS | ROYAL OAK
L3
CR
111
L3
L3
CR
110
GIRLS
--
JC
STAFF T
--
--
STUDENT SERVICES
115
IT
WKRM
--
--
BOYS
--
L3
VE SCOPCER: WHERE "L1" TAG IS USED, ACCOUNT FOR
EM BATT1E0R4 Y-POWERED FIXTURE FOR EMERGENCY
LIGHTING IN LIEU OF UL924 DEVICE.
HALF SHADED FIXTURE = BATTERY-POWERED LIGHT
L3
L3
CR
105
LIGHTING GENERAL NOTES
1. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATION OF ALL
LIGHTING FIXTURES UNLESS OTHERWISE NOTED.
2. EXIT LIGHTS AND EMERGENCY BATTERY UNITS SHALL BE UNCONTROLLED AND TIED
AHEAD OF LOCAL AREA LIGHTING SWITCH, UNLESS CIRCUITED OTHERWISE.
3. WHERE MORE THAN ONE LIGHT SWITCH IS INDICATED TO BE INSTALLED AT THE SAME
LOCATION, THEY SHALL BE GROUPED UNDER ONE COMMON FACEPLATE.
4. ALL POWER PACKS TO BE LOCATED DIRECTLY ABOVE SWITCH.
5. LIGHT FIXTURES ARE LOOPED TOGETHER TO INDICATE CONTROL ZONE GROUPS.
CONNECTED FIXTURES ARE TO BE CONTROLLED TOGETHER. CIRCUITS MAY BE SHARED
AMONG SEPARATE CONTROL ZONE GROUPS. MULTIPLE ZONES ZONES MAY BE COMBINED
IN SOFTWARE TO FORM SCENES. SEE LIGHTING CONTROL MATRIX: SCENE SCHEDULE (IF
PROVIDED), AND PANEL SCHEDULES FOR ADDITIONAL INFORMATION.
6. ALL CONDUITS SHALL BE ROUTED CONCEALED UNLESS NOTED OTHERWISE.
LIGHTING KEYNOTES
L1 PROVIDE UL924 LISTED GENERATOR/EMERGENCY TRANSFER DEVICE FOR FIXTURE OR
CIRCUIT AS INDICATED.
L2 NEW LIGHT FIXTURE(S) SHALL BE CONNECTED TO EXISTING BRANCH CIRCUIT IN SPACE.
L3 REMOVE AND REINSTALL LIGHTING FIXTURE(S) IN AREA AS REQUIRED TO ACCOMMODATE
WORK BY OTHER TRADES.
L4 HATCHED HEX INDICATES ACOUSTIC-ONLY FIXTURE. FELT COLOR FINISH AS INDICATED ON
PLAN (Y = YELLOW, B = BLUE). COORDINATE INSTALLATION WITH INTERIORS DRAWINGS.
ALL EXTERIOR LIGHTING SHALL BE CONTROLLED BY BMS SYSTEM.
REFER TO LIGHTING CONTROL MATRIX (SHEET E0.0) FOR INTERIOR SPACES.
ISSUANCES
CONSTRUCTION DOCUMENTS
VE MARKUPS
DATE
11.06.2025
12.22.2025
CR
CR
109
108
L3
L3
CR
CR
107
106
L3
L3
ELECTRICAL LIGHTING PLAN - UNIT 100
SCALE: 1/8" = 1'-0"
TE OF M I CHI
SCOTT E.
TOWNSEND
ENGINEER
No.
6201050400
PROF ESSI ON A L E
11/06/2025
Strategic Energy Solutions®
4000 W. Eleven Mile Road Berkley, MI 48072
Phone 248.399.1900 Fax 248.399.1901
www.sesnet.com
© 2025 SES, INC.
SES Project # 23 0588 02
KEY PLAN
JOB NO. 2900.09.D
N
SHEET TITLE
ELECTRICAL LIGHTING PLAN -
UNIT 100
SHEET NO.
EL1.1
C KINGSCOTT ASSOCIATES INC.
KALAMAZOO, MICHIGAN
* Disclaimer: Government BidHub provides information on bids, RFPs (Requests for Proposals), and RFQs (Requests for Qualifications) solely for convenience and informational purposes. This site is not an official public notice board. For official details, responses, or inquiries, please contact the relevant government agency directly.

Government Bids

Empower Your Bidding Strategy

Unlock Government BidHub's unparalleled access to high-quality, tailored bid information.

  • Access an extensive database of bids, including comprehensive local and state opportunities.
  • Receive customized alerts for the bids that matter most to your business.
  • Explore detailed specifications to ensure precise and competitive submissions.
  • Gain a competitive edge with up-to-date information and exclusive opportunities.

See Also

00302 I-9 & E-Verify

Release Date Project with Bid Documentation Mandatory Pre-Bid Site Visit Bid Due Date

Oakland University

Bid Due: 7/08/2026

FORM 5550 #10 FF WINDOW COLLE...

Description: FORM 5550 #10 FF WINDOW COLLECTIONS ENVELOPE Department: Technology, Management and Budget

State of Michigan

Bid Due: 7/17/2026